Leasson testing

Already Listed Asset Type or Treatment
Add New Asset
What compromised it
Solution
Photo
User ID (Post author)
Being blocked by external scaffold
Inform method statements
Black Box Admin
Being forced open by occupiers/smokers
Education of occupiers
Black Box Admin
Rooflight used to access roof
Upgrade actuator
Black Box Admin
Closer disconnected
Record torque and speed of closing
Black Box Admin
Painted or warning sticker removed
Education of occupiers
Black Box Admin
New flooring fitted, creating gap
Training, inspection and sign-off
Black Box Admin
Compressed air being used to flush water but creating oxidisation and leaks
Standardised tasks and training
Black Box Admin
New door bell fitted, compromising penetration
Education of occupiers
Black Box Admin
30 min foam used on 60 min door or damper
Training, inspection and sign-off
Black Box Admin
Water ingress damaging fire integrity
Inspection and better asset records
Black Box Admin
Smoke seal on door damaged when easing a non-closing fire door
Training, inspection and sign-off
Black Box Admin
Fire stopping deteriorated due to water ingress
Fix leak and replace fire stopping
Black Box Admin
Collar installed within batt then angle used to ‘support’ it but using drywall or wood screws and threaded rod with bolts unlikely to have come from a tested solution
https://bim4housing-blackbox.com/wp-content/uploads/formidable/2/Color-INstalled-3-150x150.jpg
Black Box Admin
Pipe fouling the wall, pipe in first
https://bim4housing-blackbox.com/wp-content/uploads/formidable/2/Pipe-fouling-1-150x150.jpg
Black Box Admin
Inappropriate use of ‘fire rated foam’
https://bim4housing-blackbox.com/wp-content/uploads/formidable/2/Inappropriate-use-1-150x150.jpg
Black Box Admin
Inappropriate use of ‘fire rated foam’
https://bim4housing-blackbox.com/wp-content/uploads/formidable/2/fe-150x150.jpg
Black Box Admin
Firestop services at floor level, through installed services
https://bim4housing-blackbox.com/wp-content/uploads/formidable/2/firestop-services-2-150x150.jpg
Black Box Admin
Pipe chase with no closers installed before boxing in
https://bim4housing-blackbox.com/wp-content/uploads/formidable/2/Pipe-chase-1-150x150.jpg
Black Box Admin
Edges not coated on top level, firestop products unlikely to be tested for services, not sealed correctly to prevent smoke etc
https://bim4housing-blackbox.com/wp-content/uploads/formidable/2/Edges-2-150x150.jpg
Black Box Admin
Dry board joints and inappropriately sealed services
https://bim4housing-blackbox.com/wp-content/uploads/formidable/2/dry-board-1-150x150.jpg
Black Box Admin