Already Listed Asset Type or Treatment | Add New Asset | What compromised it | Solution | Photo |
---|---|---|---|---|
AOV | Being blocked by external scaffold | Inform method statements | ||
AOVs | Being forced open by occupiers/smokers | Education of occupiers | ||
AOV | Rooflight used to access roof | Upgrade actuator | ||
Fire Door | Closer disconnected | Record torque and speed of closing | ||
Fire Door | Painted or warning sticker removed | Education of occupiers | ||
Fire Door | New flooring fitted, creating gap | Training, inspection and sign-off | ||
Sprinklers | Compressed air being used to flush water but creating oxidisation and leaks | Standardised tasks and training | ||
Fire Door | New door bell fitted, compromising penetration | Education of occupiers | ||
Compartmentation | 30 min foam used on 60 min door or damper | Training, inspection and sign-off | ||
Compartmentation | Water ingress damaging fire integrity | Inspection and better asset records | ||
Smoke control | Smoke seal on door damaged when easing a non-closing fire door | Training, inspection and sign-off | ||
Cladding | Fire stopping deteriorated due to water ingress | Fix leak and replace fire stopping | ||
Penetration Seals | Collar installed within batt then angle used to ‘support’ it but using drywall or wood screws and threaded rod with bolts unlikely to have come from a tested solution | |||
Penetration Seals | Pipe fouling the wall, pipe in first | |||
Penetration Seals | Inappropriate use of ‘fire rated foam’ | |||
Penetration Seals | Inappropriate use of ‘fire rated foam’ | |||
Penetration Seals | Firestop services at floor level, through installed services | |||
Penetration Seals | Pipe chase with no closers installed before boxing in | |||
Penetration Seals | Edges not coated on top level, firestop products unlikely to be tested for services, not sealed correctly to prevent smoke etc | |||
Penetration Seals | Dry board joints and inappropriately sealed services | |||
Penetration Seals | Dry board joints and inappropriately sealed services, no seal within tray | |||
Penetration Seals | Dry board joints, likely to be combustible insulation passing through without proper sealing /closer | |||
Penetration Seals | No sealing of services, | |||
Penetration Seals | No sealing of services, batt stops and then suspended ceiling, batt cannot compression fit against suspended ceiling | |||
Penetration Seals | No batt behind the duct, therefore the batt installed is ineffective both above and below the product | |||
Penetration Seals | Dry board joints, no closer and exposed metal | |||
Penetration Seals | Boards have fallen out therefore indicative of dry installation, mastic used as a mortar to secure in place | |||
Penetration Seals | Close proximity of other elements of structure limit access for air seal / fire stop | |||
Penetration Seals | Access to wallhead after services installed | |||
Penetration Seals | Interface of wall, deck and partition leaving void along length of block wall | |||
Penetration Seals | Inappropriate sealing of partition wall | |||
Penetration Seals | Riser still to be sealed at floor level, | |||
Penetration Seals | Inside of riser, damaged walls, not taped and filled, timber penetrations unprotected, no access to seal, combustible soffit of riser, plastic pipe passing through wall with no closer | |||
Penetration Seals | Out of line damper, gaps in wall |